200V Class | Motor Rating | [HP] | 0.5 | 1 | 2 | 3 |
[kW] | 0.4 | 0.75 | 1.5 | 2.2 |
Output ratings | Capacity[kVA] | 0.95 | 0.95 | 3.0 | 4.5 |
FLA[A] | 2.5 | 0.95 | 3.0 | 4.5 |
Output frequency | 0 ~ 400Hz |
Output voltage | 3 Phasde200~230V |
Input ratings | Voltage | Single phase 200 ~ 230 V (±10%) |
FLA[A] | 5.5 | 9.2 | 16 | 21.6 |
Frequency | 50 ~ 60 Hz (± 5%) |
Control | Control method | V/F control, Sersorless vector control |
Frequency setting resolution | Digital reference: 0.01Hz Analog referency: 0.06Hz/60Hz |
Frequency setting resolution | Digital reference: 0.01Hz Analog referency: 0.06Hz/60Hz |
V/F ratio | Linear, Square pattern, User V/F |
Overload capacity | 1 min at 150%, 30 sec at 200% (with inverse characteristic) |
Torque boost | Manual torque boost (0~15 adjustable), auto torque boost |
Input signal | Operation method | Keypad / Terminal / Communications |
Frequency setting | Analog: 0~10V / 4~20mA, Digital: Keypad, Communication: RS485 (Option) |
Start signal | Forward, Reverse |
Multi-step accel/decal time | 0.1~6000 sec. Max. 8 types available by multi-function terminal, Selectable accel/decel patterns : Linear, U and S |
Emergency stop | Interrupting the output of the drive. |
Jog | Jog operation |
Fault reset | Reset the fault when protective function is active |
Output signal | Operation status & fault output | Frequency detection, Overload alarm, Stalling, Overvoltage, Undervoltage, Drive overheating, Run, Stop, Constant speed, Speed searching, Fault output ( Relay and Open collector output ) |
Indicator | Choose one from output frequency, current, voltage and DC voltage.(Output voltage : 0~10V ) |
Operation function | DC braking, Frequency limit, Frequency jump, Second function, Slip compensation, Reversing prevention, Auto restart, PID control |
Protection functions | Drive trip | Overvoltage, Undervoltage, Overcurrent, Drive overtemperature, Motor overtemperature, I/O phase loss, I/O mis-wiring, Overload , External device fault 1.2, Loss of speed command, Hardware fault, Communication error, CPU error |
Drive alarm | Stall prevention, Overload alarm |
Momentary power loss | Less than 15 msec: keeping operation More than 15 msec: auto restart available |
Display Keypad | Operation information | Output frequency, current and voltage, Set frequency value, Operation speed, DC voltage |
Trip information | Display the trip cause when the protection function activates. Recent 5 faults records stored |
Environment | Ambient temperature | -10 ~ 40℃ |
Storage temperature | -20 ~ 65℃ |
Humidity | 90 %RH max (No condensing) |
Atmosphere | No corrosive gas, flammable gas, oil mist or dust |
Pressure | 70 ~ 106k Pa |