| Protection | Over current, Lock/Stall, Phase failure, Phase unbalance, Reverse phase, Under current, Ground
fault, Short circuit |
|---|
| Connection method | Extention type |
|---|
| Operating time characteristics | Heat accumulation inverse time / inverse time / definite time |
|---|
| Rated current | 0.5~10A/5~100A (Separate) |
|---|
| Display | 4 digit, 7-Segment |
|---|
| Operating power | AC/DC 85~245V (50Hz/60Hz) |
|---|
| Reset method | Automatic | 1~20min |
|---|
| Manual / Electrical | On/Off selectable |
|---|
| Installation / installation method | Display can be installed separately, 35mm DIN rail / Screw installation |
|---|
| Tolerance | Current | ±5% |
|---|
| Time | ±5% |
|---|
| 4~20mA output | ±5% |
|---|
| Time setting | Startup delay | 1~200sec |
|---|
| Operation delay | 1~60sec |
|---|
| Aux. contact | Composition | 3-SPST(Power supply 1a1b, instantaneous operation 1a) |
|---|
| Capacity | 3A/250VAC Resistive Load |
|---|
| Contact minimum load | 100mA / 5VDC |
|---|
| ZCT Input | 200mA/100mV(Exclusive ZCT) |
|---|
| Environment | Operation | -10℃ ~ 55℃ |
|---|
| Storage | -20℃ ~ 70℃ |
|---|
| Relative humidity | Below 80% RH (No freezing) |
|---|
| Insulation resistance | 100Mohm/500VDC |
|---|
| Fast transient | 2kV/1Min |
|---|
| Power consumption | Below 2W |
|---|
| Certification | CE |
|---|