GIPAM3000

Multifunctional digital power protection monitoring device with various protection elements and measurement elements

Features

Protection Function

  • With 34 types of protection elements in 2 models, the distribution system fully protected
  • Enhanced analysis function through various saved event data (up to 1,000 events are saved)
  • Trip logic and sequence with Programmable Logic Controller and 1,024 in/output port
  • Extended power quality monitoring
  • Select Before Operating (SBO) and Check Before Operating (CBO)
  • Vector diagram
  • Trip Circuit Supervision (TCS) and Trip Relay Supervision (TRS)
  • Sequence of Event (SOE)
  • PT (VT) failure detection
  • Circuit Breaker Failure (CBF)
  • Cold Load Pickup (CLP)
  • Root Mean Square (RMS) trend
  • Disk emulation

Convenience Function

  • Self-diagnosis and sequence monitoring
  • HMI with enhanced visibility and convenience
  • Convenient lever withdrawal structure
  • Long-life and reliable parts applied
  • Fully compatible with previous models (GIPAM2000/2200)

Communication Function

  • Various communication compatibility (MODBUS, DNP, IEC61850)
  • Remote access using PC Manager

Specification

Protection factor

TypeUsageProtection
GIPAM3000 FIFeeder/Incoming

Motor

Distributed Generator
OCR (50/51)
SEL (51S) Note1)
UVRR (27R)
OVGR (64) Note3)
DPR (32P)
UFR (81U)
NSOCR (46)
UPR (37)
RECLOSING (79)
PTF (60F)
OCGR (50/51N)
DOCGR (67NI/67ND)Note1)
OVR (59)
NSOVR (47N)
DQR (32Q)
OFR (81O)
THR (49)
UVR (37)
NCH (66)
CLP
SGR (67G)
UVR (27)
OVRR (59R)
POR (47P)
DOCR (67I/67D)
ROCOF (81R)
STALL/LOCK (48/51LR)
SYNC (25)
CBF (50BF)
LOCK-OUT (86)Note4)
GIPAM3000 TTransformerOCR (50/51w1)
OCGR (50/51N-1)
DFRG (87N)
OCR (50/51w2)
OCGR (50/51N-2)
LOCK-OUT (86)Note4)
OCR (50/51w3)
DFR (87T)Note5)

Note) 1. Sensitive Earth Fault (SEF) is a relay element that detects the earth current in the event of an earth accident in the non-ground
           2. DOCGR is the same as DGR.
           3. OVGR is ALRAM with no breaker TRIP In factory-shipped products
           4. Lock-out (86) can be configured with PLC Trip Logic
           5. The Inrush Detector (68) element is included in the DFR (87T) elemen

Specification

TypeSpecification
Wiring3P3W (2PT-D), 3P4W (3PT-Y)
RatingFrequancy60Hz, 50Hz Note)
VoltagePT110V (55~125V)
GPTVn*√3 Vn: PT secondary rating voltage
CurrentCT5A
ZCT1.5mA
PowerAC/DC110V, DC125V
Power consumption30W or less: Stanby / 50W or less: Operation
Burden0.5VA or less: PT
1.0VA or less: CT
Input contactfor generalDigital Input AC/DC 110V, DC125V
Output contactfor tripAC 250V 16A/DC 30V 16A, Resistive Load: Rated Capacity
AC 4000VA, DC 480W: Opening Capacity
for alarmAC 250V 5A/DC 30V 5A, Resistive Load: Closed Capacity
AC 1250VA, DC 150W: Opening Capacity
ToleranceOperation Value±5%
Operation Time±5% or ±35ms
OInsulation ResistanceDC 500V 100MΩ or more
Insulation VoltageAC 2kV (1kV)/1min
Lightning impulse voltageAC 5kV (3kV) or more, 1.2x50μs standard waveform supplied
Overload withstandCurrent circuitWithstand 1.2 times of rated current continuously
Withstand 2 times of rated current for 3 hours.
Withstand 20 times of rated current for 2 seconds.
Withstand 40 times of rated current for 1 second.
Voltage circuitWithstand 1.15 times of rated voltage for 3 hours.
Fast Transient Disturbance4kV: power input
2kV: other input
Electrostatic Discharge (ESD)8kV: Air, 6kV: Contact
TemperatureOperation-25℃ ~ 60℃
Storage-40℃ ~ 70℃
HumidityRH 80% or less (non-condensing)
Altitude2,000m or less
EnvironmentA place not subject to abnormal vibration and shock.
Applied StandardsKEMC 1120
IEC 61000-4-2 ~ 4-6, 4-8, 4-11, 4-16, 4-17, 4-18, 4-29
CISPR 11, 22
IEC 60255-26
IEC 61850-6, 7-1, 7-2, 7-3, 7-4, and 8-1
Dimension (mm)209 (W)x185.8 (D)x260 (H): Cutting Size
Weignt10.3kg
CommunicationRS485: Modbus, DNP3.0
Ethernet TE: Modbus, DNP3.0, IEC61850
Ethernet FE: Modbus, DNP3.0, IEC61850

Note) Contact us.

All in one

Hanoi Office

10th floor, 789 building, 147 Hoang Quoc Viet street, Cau Giay District, Ha Noi city, Vietnam

Hai Phong

LGE Factory - Tràng Duệ Industrial - An Dương District, Hải Phòng City

Da Nang

Văn phòng đối tác (HVN) 305 - Nguyễn Tất Thành - Hải Châu - Đà Nẵng

Ho Chi Minh Office

17th floor, Empress building, 138-142 Hai Ba Trung street, Da Kao ward, Distric 1, Ho Chi Minh city, Vietnam

Log in

Welcome to LS Electric