Protection funtions | Overcurrent, phase fail, phase unbalance, stall, locked rotor, reverse phase, ground fault (Type
option)Instance (Type option) |
---|
Connection method | Penetrated / Terminaltype |
---|
Operating time characteristics | Thermal heat build-up inverse time / Non-thermal heat build-up inverse time / Definite time |
---|
Rated current | 0.5~6A/5~65A(Rating option upon placing an order) |
---|
Display | 4 digit, 7-Segment |
---|
Operating power | AC/DC 85~260V(50Hz/60Hz) |
---|
Reset method | Automatic | 1~20min (only for overcurrent) |
---|
Manual | (Electrical reset) |
---|
Installation / Mounting method | Display can be installed separately, 35mm DIN rail / Screw installation |
---|
Tolerance | Current | ±3% |
---|
Time | ±5% |
---|
4~20mA output | ±5% |
---|
Time setting | Startup delay | 1~200sec |
---|
Operation delay | 1~60sec |
---|
Aux. contact | Composition | 3-SPST(Power supply 1a1b, i nstantaneous operation 1a) |
---|
Capacity | 3A/250VAC Resistive Load |
---|
Contact minimum load | 100mA / 6VDC : (95-996, 97-98) |
---|
10mA / 5VDC ( 07-08) |
ZCT Input | External | 200mA/100mV(Exclusive ZCT) |
---|
Built-in | Support (Separate connection unnecessary |
---|
Service environment | Service temperature | -20℃ ~ 60℃ |
---|
Storage temperature | -30℃ ~ 70℃ |
---|
Relative humidity | Below 50% RH (Without condensation) |
---|
Insulation resistance | 100MΩ/500VDC |
---|
Lightning impulse voltage | 1.2X50us 5kV Prototype waveform supply |
---|
Fast transient | 2kV/1Min |
---|
Power consumption | Below 2W |
---|