| Wirings | 1P2W, 1P3W, 3P3W, 3P4W |
|---|
| Input | Frequency | 50Hz/60Hz |
|---|
| Voltage | PT | 10~230V |
|---|
| GPT | 2.2~230V |
|---|
| Current | CT | 0.05~6A |
|---|
| Control Voltage | AC/DC 110V |
|---|
| Power Consumption | Max. 30W |
|---|
| Burden | PT | Max. 1.0VA |
|---|
| CT | Max. 1.0VA |
|---|
| Input contact 10EA | Digital Input : AC/DC 110V |
|---|
| Output contact | 2EA for power | AC230V 16A / DC30V 16A, Resistive load 3680VA, 480W |
|---|
AC230V 8A / DC30V 8A, Inductive load(cosø=0.4, L/R=7ms) 1840VA, 240W |
| 8EA for alarm | AC230V 12A / DC25V 12A, Resistive load 2760VA, 300W |
|---|
AC230V 6A / DC25V 6A, Inductive load(cosø=0.4, L/R=7ms) 1880VA, 150W |
| Insulation Resistance | Over DC 500V 100㏁ |
|---|
| Insulation Voltage | AC 2kV (1kV) / for 1 min |
|---|
| Impulse Voltage | AC 5kV (3kV) Over 1.2×50㎲ |
|---|
| Overload Withstand | Current circuit | 2 In for 3 hours 20 In for 2 seconds |
|---|
| Voltage circuit | 1.15 Vn for 3 hours |
|---|
| Fast Transient Disturbance | Power Input 4kV Other Input 2kV (Analog Input 1kV) |
|---|
| ESD (Electrostatic Discharge) | Air 8kV Contact 6kV |
|---|
| Operation temperature | -10℃ ~ 55℃ |
|---|
| Storage Temperature | -25℃ ~ 70℃ |
|---|
| Humidity | Within 80% RH, no condensation |
|---|
| Altitude | 1000m and below |
|---|
| Others | Non-impact place Non-air pollution place |
|---|
| Standard | IEC 60255, IEC 61326, IEC 61000-4, KEMC 1110 |
|---|
| Communication | MODBUS/RS-485, I-NET |
|---|
| Dimension (W×H×D) | 190×255×116 (mm) |
|---|
| Weight | 3.6kg |
|---|