Wirings | 1P2W, 1P3W, 3P3W, 3P4W |
---|
Input | Frequency | 50Hz/60Hz |
---|
Voltage | PT | 10~230V |
---|
GPT | 2.2~230V |
---|
Current | CT | 0.05~6A |
---|
Control Voltage | AC/DC 110V |
---|
Power Consumption | Max. 30W |
---|
Burden | PT | Max. 1.0VA |
---|
CT | Max. 1.0VA |
---|
Input contact 10EA | Digital Input : AC/DC 110V |
---|
Output contact | 2EA for power | AC230V 16A / DC30V 16A, Resistive load
3680VA, 480W |
---|
AC230V 8A / DC30V 8A, Inductive load(cosø=0.4, L/R=7ms)
1840VA, 240W |
8EA for alarm | AC230V 12A / DC25V 12A, Resistive load
2760VA, 300W |
---|
AC230V 6A / DC25V 6A, Inductive load(cosø=0.4, L/R=7ms)
1880VA, 150W |
Insulation Resistance | Over DC 500V 100㏁ |
---|
Insulation Voltage | AC 2kV (1kV) / for 1 min |
---|
Impulse Voltage | AC 5kV (3kV) Over 1.2×50㎲ |
---|
Overload Withstand | Current circuit | 2 In for 3 hours
20 In for 2 seconds |
---|
Voltage circuit | 1.15 Vn for 3 hours |
---|
Fast Transient Disturbance | Power Input 4kV Other Input 2kV (Analog Input 1kV) |
---|
ESD (Electrostatic Discharge) | Air 8kV Contact 6kV |
---|
Operation temperature | -10℃ ~ 55℃ |
---|
Storage Temperature | -25℃ ~ 70℃ |
---|
Humidity | Within 80% RH, no condensation |
---|
Altitude | 1000m and below |
---|
Others | Non-impact place Non-air pollution place |
---|
Standard | IEC 60255, IEC 61326, IEC 61000-4, KEMC 1110 |
---|
Communication | MODBUS/RS-485, I-NET |
---|
Dimension (W×H×D) | 190×255×116 (mm) |
---|
Weight | 3.6kg |
---|