XGK, XGI CPU

Features

XGK CPU (LS Standard Ladder Programming)

Premium CPU for high-speed and large scale application


XGK-CPUUN

Processing speed: 8.5ns/step

Program capacity: 256K steps

I/O points: 6,144

I/O device point: 65,536 (Remote I/O)

XGK-CPUHN

  • Program capacity: 128K steps
  • I/O points: 6,144
  • I/O device point: 65,536 (Remote I/O)
  • Processing speed: 8.5ns/step

XGK-CPUSN

  • Program capacity: 64K steps
  • I/O points: 3,072
  • I/O device point: 65,536 (Remote I/O)
  • Processing speed: 8.5ns/step

XGK-CPUU (Ultra capacity)

  • Program capacity: 128K steps
  • I/O points: 6,144
  • I/O device point: 32,768 (Remote I/O)
  • Processing speed: 28ns/step

XGK-CPUH (High performance)

  • Program capacity: 64K steps
  • I/O points: 6,144
  • I/O device point: 32,768 (Remote I/O)
  • Processing speed: 28ns/step

XGK-CPUA (Advanced)

  • Program capacity: 32K steps
  • I/O points: 3,072
  • I/O device point: 32,768 (Remote I/O)
  • Processing speed: 28ns/step

General sequence controller PLC CPU

XGK-CPUS (Standard)

  • Program capacity: 32K steps
  • I/O points: 3,072
  • I/O device point: 32,768 (Remote I/O)
  • Processing speed: 84ns/step

XGK-CPUE (Economic)

  • Program capacity: 16K step
  • I/O point: 1,536
  • I/O device point: 32,768 (Remote I/O)
  • Processing speed: 84ns/step

XGI CPU (IEC Standard Programming)

Premium CPU for high-speed and large scale application


XGI-CPUUN

Processing speed: 8.5ns/step

Program capacity: 2MBytes

I/O points: 6,144

I/O device point: 131,072 (Remote I/O)

XGI-CPUU

  • Program capacity: 1MBytes
  • I/O points: 6,144
  • I/O device point: 131,072 (Remote I/O)
  • Processing speed: 28ns/step

XGI-CPUH

  • Program capacity: 512KBytes
  • I/O points: 6,144
  • I/O device point: 131,072 (Remote I/O)
  • Processing speed: 28ns/step

General sequence controller PLC CPU

XGI-CPUS (IEC Standard)

  • Program capacity: 128KBytes
  • I/O points: 3,072
  • I/O device point: 32,768 (Remote I/O)
  • Processing speed: 28ns/step

XGI-CPUE (IEC Standard)

  • Program capacity: 64KBytes
  • I/O points: 1,536
  • I/O device point: 32,768 (Remote I/O)
  • Processing speed: 84ns/step

Specification

XGK CPU
ItemDescriptionRemarks
XGK-CPUUNXGK-CPUHNXGK-CPUSN
Operation methodCyclic execution of stored program, Time-driven interrupt, Process-driven interrupt
I/O control methodBatch processing by scan synchronization (Refresh), Direct input/output by instruction
Program languageLadder diagram, Instruction list, SFC(Sequential Function Chart), ST(Structured Text)
Number of instructionsBasic40
Application700
Processing speedLD0.0085㎲/step
MOVE0.255㎲/step
Real number operation± : 182.2ns(S), 327.3ns(D)S: Single real number D: Double real number
X : 336ns(S), 427ns(D)
÷ : 345ns(S), 808ns(D)
Program capacity256Kstep (2,048KB)128Kstep (1,024KB)64Kstep (512KB)
I/O points(availableto install)6,1446,1443,072
Data areaPP00000 ~ P4095F(65,536 points )
MM00000 ~ M4095F(65,536 points )
KK00000 ~ K4095F(65,536 points )
LL0000 ~ L11263F(180,224 points )
FF0000 ~ F4095F(65,536 points )
T100ms : T0000 - T2999Timer (Adjustable)
10ms : T3000 - T5999
1ms : T6000 - T7999
0.1ms : T8000 - T8191
CC0000 ~ C4095
SS00.00 ~ S255.99
DD0000 ~ D524287D0000 ~ D262143
UU0.0~U7F.31U0.0~U3F.31Special module data refresh area
Z256 points
NN00000 ~ N21503
R16 block8 block2 block32Kwordper1block(R0~R32767)
Flash area2M byte, 32 blocksControllable by R device
Program typeTotal program256
Initialization1 (_INT)
Time-driven32
Internal32
Operation modeRUN, STOP, DEBUG
Self-diagnosisExecution, Delay, Memory error, I/O error, Battery error, Power errorModbus slave
Programming portRS-232C (1Ch), USB (1Ch)
Data retention at power failureSet “retain” at data declaration
Max. expansion stage73Total length 15m
Current consumption (mA)960
Weight (Kg)0.12
ItemDescriptionRemarks
XGK-CPUUXGK-CPUHXGK-CPUAXGK-CPUSXGK-CPUE
Operation methodCyclic execution of stored program, Time-driven interrupt, Process-driven interrupt-
I/O control methodBatch processing by scan synchronization (Refresh), Direct input/output by instruction-
Program languageLadder diagram, Instruction list, SFC(Sequential Function Chart), ST(Structured Text)-
Number of instructionsBasic40-
Application700-
Processing speedLD0.028㎲/Step0.084㎲/Step-
MOVE0.084㎲/Step0.252㎲/Step-
Real number operation ± : 0.602㎲(S), 1.078㎲(D)
X : 1.106㎲(S), 2.394㎲(D)
÷ : 1.134㎲(S), 2.66㎲(D)
± : 1.442㎲(S), 2.87㎲(D)
X : 1.948㎲(S), 4.186㎲(D)
÷ : 1.442㎲(S), 4.2㎲(D)
S: Single real number D: Double real number
Program capacity128Kstep(512KB)64Kstep(256KB)32Kstep(128KB)16Kstep(64KB)-
I/O points(availableto install)6,1443,0721,536-
Data areaPP00000 ~ P2047F(32,768 points)-
MM00000 ~ M2047F(32,768 points)-
KK00000 ~ K2047F(32,768 points)-
LL0000 ~ L11263F(180,224 points)-
FF0000 ~ F2047F(32,768 points)-
T 10ms : T1000 - T1499  100ms : T0000 - T0999
1ms : T2000 - T2047  1ms : T1500 - T1999
-
CC0000 ~ C2047
SS00.00 ~ S127.99
DD0000 ~ D32,767D0000 ~ D19,999
UU0.0~U7F.31U0.0~U3F.31U0.0~U3F.31U0.0~U1F.31Special module data refresh area
Z128 points
NN00000 ~ N21503-
R2 block1 block32Kwordper1block(R0~R32767)
Flash area2M byte, 32 blocksControllable by R device
Program typeTotal program256
Initialization1 (_INT)
Time-driven32
Internal32
Operation modeRUN, STOP, DEBUG
Self-diagnosisExecution, Delay, Memory error, I/O error, Battery error, Power errorModbus slave
Programming portRS-232C (1Ch), USB (1Ch)
Data retention at power failureSet “retain” at data declaration
Max. expansion stage731Total length 15m
Current consumption (mA)960940
Weight (Kg)0.12
XGI CPU
ItemXGI-CPUUNXGI-CPUU/DXGI-CPUUXGI-CPUHXGI-CPUSXGI-CPUERemarks
Operation systemReiterative operation, fixed cycle operation, constant scan
I/O Control systemScan synchronous batch processing system(refresh system), direct system by command
Program languageLadder Diagram, SFC (Sequential Function Chart), ST (Structured Text)
Operation processing speed (basic command)Operator18
Basic function136 types + real number operation function
Basic function block43
Dedicated function blockDedicated function blocks by special function modules, communication dedicated function block(P2P)
Basic0.0085㎲/step0.028㎲/step0.084㎲/step
MOVE0.255㎲/step0.084㎲/step0.252㎲/step
Real number operation ± : 0.119㎲(S), 0.281㎲(D)
X : 0.272㎲(S), 0.680㎲(D)
÷ : 0.281㎲(S), 0.685㎲(D)
± : 0.392㎲(S), 0.924㎲(D)
X : 0.896㎲(S), 2.240㎲(D)
÷ : 0.924㎲(S), 2.254㎲(D)
± : 1.442㎲(S), 2.87㎲(D)
X : 1.948㎲(S), 4.186㎲(D)
÷ : 1.442㎲(S), 4.2㎲(D)
S: Single real number D: Double real number
Program memory capacity2M1M512KB128KB64KB
I/O points (installable)6,144 points3,072 points1,536 points
Max. I/O memory contact131,072 points32,768 points
Data memorySymbolic variable area(A)1024KB (max. 512KB retain settable)512KB (max. 256KB retain settable)128KB (max. 64KB retain settable)64KB (max. 32KB retain settable)
I variable(I)16KB4KB
Q variable(I)16KB4KB
Direct variableM512KB (max. 256KB retain settable)256KB (max. 128KB retain settable)64KB (max. 32KB retain settable)32KB (max. 16KB retain settable)
R64KB X 16block64KB X 2block64KB X 1block32KB X 1block
W1,024KB128KB64KByte32KByteR
Flag variableF8KB4KBSystem flag
K16KB4KBPID flag
L22KBHigh speed link flag
N42KBP2PParameters
U8KB4KB2KBAnalog data Refresh
Flash area2MB, 32block1MB, 16block
TimerNo point limit
Time range: 0.001~ 4,294,967.295 second(1,193 hours)
20 bytes of symbolic variable area per point
CounterNo point limit Coefficient range : 64 bit expression8 bytes of symbolic variable area per point
Program structureTotal no. of programs256
Initialization task1
Fixed cycle task32
Internal device task32
Operation modeRUN, STOP, DEBUG
Restart modeCold, Warm
Self diagnosisOperation delay monitoring, memory fault, I/O fault, battery fault, power fault and etc
Data protection in case of power failureRetain area setting by basic parameters
Max. base extension731Total length 15m
Current consumption(mA)960mA940mA
Weight (kg)0.12kg
XGK/XGI CPU built-in Ethernet specification
ItemXGK-CPUSN, CPUHN, CPUUN / XGI-CPUUNRemarks
EthernetFeature1 Port-
10/100BASE-TX-
Auto negotiation (Full-duplex and half duplex)-
Auto MDIX Crossover-
Max. Support 4 channelSupport 8Kbyte each send and receive channel
Max. Distance between nodes : 100m-
Max. Protocol size : 1500ByteIP Fragmentation is not supported.
CableUTP, STP, FTP cables is availableFTP, STP is recommended to prevent noise
ServiceSetting communication parameters with XG5000-
Loader service (XG5000 connection) supportedRemote stage 1 connection with PLC is available
LS protocol(XGT) supported.Server & TCP supported. Client & UDP not supported.
Other company’s protocol (Modbus TCP/IP) supported
All in one

Hanoi Office

10th floor, 789 building, 147 Hoang Quoc Viet street, Cau Giay District, Ha Noi city, Vietnam