| Wirings | 1P2W, 1P3W, 3P3W, 3P4W |
|---|
| Input | Frequency | 50Hz/60Hz |
|---|
| Voltage | PT | 10~230V (110V) |
|---|
| GPT | 2.2~230V |
|---|
| Current | CT | 0.05~6A or 0.01~1.2 (1A) |
|---|
| Control voltage | AC/DC 110V or AC/DC 220V |
|---|
| Power consumption | Max. 30W |
|---|
| Burden | PT | Max. 1.0VA |
|---|
| CT | Max. 1.0VA |
|---|
| Input contact 10EA | Digital Input : AC/DC 110V or AC/DC 220V |
|---|
| Output contact | 2EA for power | AC 250V 16A/DC 30V 16A 3840VA/480W |
|---|
| 8EA for alarm | AC 250V 16A/DC 30V 16A 3840VA/480W |
|---|
| Insulation Resistance Over | DC 500V 100㏁ |
|---|
| Insulation Voltage | AC 2kV (1kV) / 1min |
|---|
| Impulse Voltage | AC 5kV (3kV) / 1.2×50㎲ |
|---|
| Overload withstand | Current circuit | 1.2 In for 3 hours 8 In for 2 seconds |
|---|
| Voltage circuit | 1.15 Vn for 3 hours |
|---|
| Fast Transient/Burst Immunity | Power Input 4kV (PT, CT) Other Input 2kV (Analog Input 1kV) |
|---|
| ESD(Electrostatic Discharge) | Air 8kV Contact 6kV |
|---|
| Operation temperature | -10℃ ~ 55℃ |
|---|
| Storage temperature | -25℃ ~ 70℃ |
|---|
| Humidity Average | Within 80% RH, no condensation |
|---|
| Altitude | 2000m and below |
|---|
| Others | Non-impact place Non-air pollution place |
|---|
| Standard | IEC 60255, IEC 61000-4 |
|---|
| Communication | Modbus/RS485, Ethernet IEC61850 MMS/Ethernet |
|---|
| Dimension(W×H×D) | 190×255×116 (mm) |
|---|
| Weight | 3.6 kg |
|---|